ports |
flanges PN 40 |
function |
NC |
pressure range |
0-40 bar |
KV value |
13,0 m³/h |
media |
liquid fuels |
flow direction |
A B as marked |
switching cycles |
130 1/min |
switching time |
opening 130 ms closing 130 ms |
media temperature |
DC -10 °C — +140 °C
AC -10 °C — +140 °C |
ambient temperature |
DC -10 °C — +60 °C
AC -10 °C — +60 °C |
weight |
10,5 kg |
nominal voltage |
Un 24 V DC +5% / -10%
Un 230 V 40-60 Hz AC +5% / -10%
|
actuation |
DC direct-current magnet AC direct-current magnet with separate rectifier |
insulation rating |
H 180 °C |
protection |
IP65 |
energized duty rating |
ED 100% |
connection |
M 16 x 1,5 terminal box |
The valves' technical design is based on media and application requirements. This can lead to deviations from the general specifications shown on the data sheet with regards to the design, sealing materials and characteristics.